电子式温度控制器 | DCT 010(直流)

网站首页 > 电子式温度控制器 | DCT 010(直流)
  • High DC switching capacity
  • Adjustable temperature
  • Small hysteresis
  • Optical operating display (LED)
  • Integrated switch module
  • Precise measurement via an external sensor

The electronic thermostat with integrated switch module is used to control DC powered devices with high capacities in control and switch cabinets. Heaters, coolers, filter fans or signal devices can directly be controlled via an internal electronic circuit. The external sensor can be positioned freely anywhere in the control cabinet for precise temperature measurements. Additionally, this thermostat is available in versions that not only measure temperature via the external sensor, but also the relative humidity.

TECHNICAL DATA

DOWNLOAD PDF

Switch difference (temperature) 3 K (±1 K tolerance) at +25 °C (+77 °F), 50 % RH
Reaction time approx. 5 sec.
External sensor cable 2 m with snap in connector (included in the delivery)
Contact type contact maker NO (MOSFET) or contact breaker NC (MOSFET)
Service life > 100,000 cycles
Operating voltage DC 20 to 56 V
Optical indicator LED
Connection 6-pole terminal: stranded wire11.5 mm² (AWG 16);
max. 2.5 mm² (AWG 12)
Mounting clip for 35 mm DIN rail, EN 60715
Casing plastic according to UL94 V-0, grey (bicolor)
Dimensions 93 x 53 x 44 mm
Weight approx. 120 g (incl. sensor)
Fitting position vertical
Storage temperature -40 to +80 °C (-40 to +176 °F)
Operating/Storage humidity max. 90 % RH (non-condensing)
Protection type IP20
Approvals UL File No. E164102, VDE, EAC
Note other versions (e.g. setting ranges and °F) on request

1When connecting with stranded wires, wire end ferrules must be used.

Art. No. Max. switching capacity Operating temperature Primary switching function -
setting range temperature
Secondary switching function² - humidity setting Contact (primary)
01011.0-21 DC 13 A -30 °C to +50 °C (-22 °F to +122 °F) -10 to +50 °C - Contact maker (NO)
01011.0-22 DC 11 A -30 °C to +60 °C (-22 °F to +140 °F) 0 to +60 °C - Contact maker (NO)
01011.0-41 DC 13 A -30 °C to +50 °C (-22 °F to +122 °F) -10 to +50 °C 65 % RH pre-set Contact breaker (NC)
01011.0-42 DC 11 A -30 °C to +60 °C (-22 °F to +140 °F) 0 to +60 °C 65 % RH pre-set Contact breaker (NC)

² Versions with secondary switching function can also register the humidity and therefore offer an additional protection for electronics.
Switch difference: 4 % RH (±1 % tolerance) at +25 °C (+77 °F), 50 % RH.

TECHNICAL DRAWING



External sensor